Q1:What are the typical application scenarios of 500kVA three-phase oil immersed transformers?
*Power distribution for small and medium-sized factories;
*Electricity supply for commercial buildings, hospitals, or schools;
*Voltage conversion of rural power grids or community distribution systems;
*Power distribution at temporary construction sites.
Q2:What are the common configurations for the rated input/output voltage of a 500KVA transformer?
*High voltage side: 11kV (domestic distribution standard);
*Low voltage side: 400V (three-phase four wire system, line voltage 400V/phase voltage 230V);
Q3:How to calculate the rated current of a 500KVA transformer?
*High voltage side: I=500kV/11kV/√3=26.24A
*Low voltage side: I=500kV/0.4kV/√3=721.7A
Q4:What are the requirements for the surrounding environment during the installation of a 500KVA transformer?
*Good ventilation, keep away from flammable and explosive materials;
*The basic platform requires horizontal load-bearing capacity (with an oil content of approximately 200kg);
*Reserved heat dissipation space (with a side distance of ≥ 0.8 meters from the wall and no obstacles at the top);
*Outdoor installation requires the installation of rain covers or fences.
Q5:What is the overload capacity of a 500kVA transformer?
*Short term overload (such as within 2 hours) can reach 150% load (copper coil);
*Long term overload will accelerate insulation aging, and it is necessary to avoid operating beyond the rated capacity.
Q6:What are the key points to pay attention to in the daily maintenance of a 500KVA transformer?
*Oil level check: The oil level gauge of the oil pillow should be within the marked range;
*Oil temperature monitoring: During normal operation, the top oil temperature is ≤ 65 ° C;
*Leakage inspection: Check whether the welds and gaskets of the fuel tank are leaking oil;
*Regular tests: insulation oil withstand voltage test, winding DC resistance measurement (once a year).
Q7:How to determine if the insulation oil needs to be replaced for a 500KVA transformer?
*Breakdown voltage: below 30kV (new oil standard ≥ 35kV);
*Excessive acid value:> 0.1mg KOH/g
*High moisture content:> 20ppm
*The oil color is dark black or contains carbide particles (needs to be filtered or replaced).
Q8:Possible causes and solutions for abnormal
temperature rise of 8.500KVA transformer?
*Reason: Overload, blocked radiator, oil circulation failure, internal winding short circuit;
*Solution: Immediately reduce the load and check the load; Clean the radiator or repair the cooling system; Suspend maintenance due to internal malfunction.
Q9:What protective devices must be configured for a 500KVA transformer?
*High voltage side: drop out fuse or circuit breaker (overcurrent protection);
*Low voltage side: air switch (short circuit protection);
*Body protection: gas relay, pressure reducing valve, thermometer;
*System protection: lightning arrester (lightning protection), grounding device (grounding resistance ≤ 4 Ω).
Q10:How to choose the energy efficiency level of a 500KVA transformer when purchasing?
*Standard: According to local national energy efficiency regulations or customer requirements
*Example: The latest energy-efficient 500kVA oil immersed transformer in Europe has a no-load loss of 459W and a load loss of 3900W; Energy efficiency>99.46%